Command device
ES 14 Extreme
Cold-resistant down to -40 °C (depending on the variant)
Control panel mounting
Thermoplastic enclosure with cable
Mounting hole diameter 22.5 mm
Mounting details to EN 50047
Suitable for the food processing industry
Loading...
Found 5 results
Product
Product
Product
Product
Product
Loaded 5 from 5 results
Technical data
General technical data
- Applied standards
- EN 60947-5-1, EN ISO 13849-1, emergency stop devices: EN 60947-5-5 and EN ISO 13850
- Enclosure
- thermoplastic, glass-fibre reinforced, shockproof, self-extinguishing UL 94 V-0
- Degree of protection
- IP65/IP67/IP69 (IEC/EN 60529), depending on the variant, use only with enclosure for command devices
- B10d (10 % load)
- 60 000
- TM
- max. 20 years
- Contact material
- silver
- Switching system
- slow action, positive break NC contacts A
- Switching elements
- 2 NC contacts, type Zb
- Connection
- cable 4 x AWG 20
- Cable cross-section
- 4 x 0.56 mm²
- Rated impulse withstand voltage Uimp
- 4 kV
- Rated insulation voltage Ui
- 250 V
- Conventional thermal current Ithe
- 6 A
- Rated operating current/voltage Ie/Ue
- 6 A/250 VAC; 0.25 A/230 VDC
- Utilisation category
- AC-15; DC-13
- Short-circuit protection
- 6 A gG/gN fuse
- Ambient temperature
- –40 °C … +65 °C (depending on the variant)
- Mechanical life
- > 30 000 operations
- Operation cycles
- max. 1800/h
- Contact opening
- max. 2 x 4 mm
Downloads
Variants / Options
The following variants / options are available on request:
Cable entry on side