Product features
Thermoplastic enclosure
Mounting details to EN 50047
sWave® wireless technology
External power supply via M12 plug-in connector
Can be combined with 3-wire PNP sensors 24 VDC or external sensors or NO contacts with gold contacts
Power supply: 24 VDC
Output signal can be individually configured at the receiver
LBT - Listen before Talk Firmware
Technical data
General technical data
Applied standards
EN 60947-5-1, EN 61000-6-2, EN 61000-6-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 301 489-3, EN 300 220-2
Enclosure
thermoplastic, glass-fibre reinforced, shockproof, self-extinguishing UL 94 V-0
Tightening torque
M4 enclosure mounting screws: max 1.2 Nm
M2.5 cover screws: approx. 0.45 Nm
Degree of protection
IP67 (IEC/EN 60529), only with plugged cable
Voltage source
24 VDC
Connection
plug-in connector M12 x 1, 4-pole, A-coded
Ambient temperature
–20 °C … +65 °C
Switching frequency
max. 5 Hz
Rated operating voltage range UB
10 … 30 VDC Pin 1 and Pin 3 plug-in connector M12
Rated insulation voltage Ui
75 VDC
Rated impulse withstand voltage Uimp
0.5 kV
Rated operating current Ie
2.5 mA
Standby current
15 µA (if sensor is not connected)
Voltage drop Ue - Uout
1.5 V
Load current
max. 100 mA
Switching points
> 5 VDC (E1, E2)
Actuating time
min. 80 ms
Note
transmission of battery voltage and switching condition
Weight
90 g
Wireless technology
General
Frequency
916.5 MHz (Japan)
Data rate
66 kbps
Channel bandwidth
520 kHz
Modulation type
2-FSK
Protocol
sWave®
Wireless approvals
Japan: ? ARIB STD-T108: 204-610002
Function
Telegram rate
max. 1440 telegrams with repetitions/h
Transmission power
< 1 mW
Wireless range
max. 150 m outdoors, max. 20 m indoors
Note
status signal – can be individually configured via radio receiver (delivery state: without status signal)