Ex AZ 16 2Ö/1S
Article no.: 1210562
contact usProduct features
Ex zone 1 and 21
Thermoplastic enclosure
Multiple coding
Wiring compartment
Attention: Please state required international approvals with your order!
Notes
1 Ex"e" cable gland M20x1.5 included in delivery
The actuator is not included in the delivery of the switches
Technical data
General technical data
Applied standards
EN 60947-5-1, EN IEC 60079-0, EN 60079-1, EN IEC 60079-7, EN 60079-31, EN ISO 13849-1, EN ISO 14119
Enclosure
thermoplastic, glass-fibre reinforced, shockproof, self-extinguishing UL 94 V-0
Switch type
type 2
Coding level
low coding
Tightening torque
cover screws: 0.5 … 0.6 Nm
switch inserts M3 screw connection terminals: min. 0.6 Nm
Degree of protection
IP65 (IEC/EN 60529)
B10d (10 % load)
2 million
TM
max. 20 years
Contact material
silver
Switching system
slow action, positive break NC contacts A
Switching elements
2 NC/1 NO contact, type Zb
Connection
screw connection terminals
Cable cross-section
min. 0.2 mm² (AWG 24), max. 1.5 mm² (AWG 16)
Cable entry
3 x M20 x 1.5; use only Ex approved and certified cable glands with min. degree of protection IP67
Clamping range
7 … 12 mm
Rated impulse withstand voltage Uimp
4 kV
Rated insulation voltage Ui
250 V
Conventional thermal current Ithe
3 A
Rated operating current/voltage Ie/Ue
3 A/250 VAC; 0.25 A/230 VDC
Utilisation category
AC-15; DC-13
Short-circuit protection
3 A gG/gN fuse
Positive break travel
9 mm
Ambient temperature
T6: –20 °C … +55 °C;
T5: –20 °C … +70 °C
Mechanical life
> 1 million operations
Impact energy
max. 7 J
Ex marking
L II 2G Ex de IIC T6/T5 Gb,
L II 2D Ex tb IIIC T80 °C/T95 °C Db
IECEx Ex de IIC T6/T5 Gb,
Ex tb IIIC T80 °C/T95 °C Db
Approvals
PTB 13 ATEX 1008 X
IECEx PTB 13.0014X
Üa
Weight
154 g