Wireless receiver

RF Rx - 4S 48V


  • sWave® wireless technology (SW868/SW915/SW917/SW922)

  • 4 potential-free optocoupler outputs

  • Transmitter/receiver assignment by teaching mode

  • LEDs for indication of switching state

Notes
  • External antenna always required for optimum wireless range

Technical data

Applied standards

EN 60947-5-1, EN 61000-6-2, EN 61000-6-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 60068-2-6, EN 60068-2-27, EN 301 489-1, EN 301 489-3, EN 300 220-1, EN 300 220-2

Enclosure

thermoplastic, glass-fibre reinforced, shockproof, self-extinguishing UL 94 V-0

Degree of protection

IP20 (IEC/EN 60529)

Number of channels

4

Mounting

DIN rail mounting

Connection

screw connection terminals 0.14 mm² - 2,5 mm², stripping length 8 mm

Inputs

2 additional push buttons (SEL, LRN)

Outputs

4 potential-free normally open contacts (optoelectronic photo relays)

Rated operating voltage range UB

12...48 VDC (-10 % ... +25 %, abs. max. 60 V)

Rated operating current Ie

48 VDC: max. 16 mA
24 VDC: max. 21 mA

Current absorption

at 48 VDC:
typ. 1.9 mA (standby current)
typ. 8 mA (1 output switched)
typ. 8 mA (2 outputs switched)
typ. 9 mA (3 outputs switched)
typ. 10 mA (4 outputs switched)

Rated operating voltage Ue

48 VDC

Rated operating current/voltage Ie/Ue

output contacts: 0.5 A / 48 VDC (abs. max. 60 V)

Utilisation category

DC-13

Wireless range

SW868/915/917:
max. 700 m outdoors,
max. 50 m indoors
SW922:
max. 230 m outdoors,
max. 25 m indoors

Display

green LED: ready for operation,
orange LED: signalling of switching state

Telegram rate

max. 12000 telegrams with repetitions/h; SW922: max. 1440 telegrams/h

Degree of pollution

2

Ambient temperature

0 °C … +55 °C

Storage and shipping temperature

–25 °C … +85 °C

Note

Inductive loads (contactors, relays etc.) are to be suppressed by suitable circuitry.
Switching contacts are not suitable for capacitive loads.
Allows configuration of LBT and status signal of the transmitters

Wireless approvals

Europe: RED 2014/53/EU
USA: FCC - XK5-RFRXSW915
Canada: IC - 5158A-RFRXSW915
Mexico: IFT - RCPSTRF17-1886
Brazil: ANATEL 04172-18-06718
Japan: ? ARIB STD-T108: 204-610002