Product features
Ex zone 1 and 21
Thermoplastic enclosure
Double insulated X
Suitable for in-line mounting
With pre-wired cable
Actuator: Long spring rod TL
Spring rod can be actuated from any direction
Spring rod can be shortened 30 mm in actuating area
Exact linear actuation not necessary
Elasticity of the spring allows for deflection above the max. switching angle of 18°
Attention: Please state required international approvals with your order!
Technical data
General technical data
Applied standards
EN 60947-5-1, EN IEC 60079-0, EN 60079-1, EN 60079-31
Enclosure
thermoplastic, glass-fibre reinforced, shockproof, self-extinguishing UL 94 V-0
Degree of protection
IP65 (EN 60079-0 + IEC/EN 60529), IP67 (IEC/EN 60529)
Contact material
silver
Switching system
slow action
Switching elements
1 NC/1 NO contact, type Zb
Connection
pre-wired cable H05VV-F
Cable cross-section
4 x 0.75 mm² (incl. conductor ferrules)
Cable length
2 m
Rated impulse withstand voltage Uimp
4 kV
Rated insulation voltage Ui
250 V
Conventional thermal current Ithe
T6: 6 A, T5: 3 A
Rated operating current/voltage Ie/Ue
6 A/250 VAC; 0.25 A/230 VDC
Utilisation category
AC-15; DC-13
Short-circuit protection
6 A gG/gN fuse
Ambient temperature
T6: –20 °C … +65 °C,
T5: –20 °C … +75 °C, +90 °C with max. 3 A
Mechanical life
> 1 million operations
Operation cycles
max. 1800/h
Repeat accuracy of switching points
± 0.1 mm
Contact opening
max. 2 x 4 mm
Impact energy
max. 7 J
Ex marking
L II 2G Ex db IIC T6/T5 Gb,
L II 2D Ex tb IIIC T80 °C/T95 °C Db
IECEx Ex db IIC T6/T5 Gb,
Ex tb IIIC T80 °C/T95 °C Db
Approvals
PTB 03 ATEX 1068 X
IECEx PTB 06.0053X
fad
Weight
208 g
Downloads
Variants / Options
The following variants / options are available on request:
Gold-plated contacts
Cable entry on side
Mechanical latching
Other cable types
Special version only for dust Ex zone 22