Ex junction/ terminal box devices

Ex AD 85 e MK5 4xM20

Article no.: 1186654Old article no.: 6711100502

Standard version
contact us

Product features

Ex
  • Ex zone 1 and 21

  • Polyester resin enclosure

  • Junction box, Ex "e" increased safety

  • Dimensions 85 x 85 x 55 mm

  • 3 x cable gland, 1 x closing plug, 4 x nut included in delivery

Technical data

Applied standards
EN IEC 60079-0, EN IEC 60079-7, EN 60079-11, EN 60079-31
Enclosure
polyester resin, glass-fibre reinforced
Tightening torque
cover screws: 1.4 Nm
Degree of protection
IP66 (IEC/EN 60529)
Connection
mantle terminals
Cable cross-section
1.5 … 4 mm²
Cable entry
4 x M20 x 1.5 (incl. 3 cable glands)
Clamping range
4 … 13 mm
Rated operating current Ie
see table
Rated operating voltage Ue
400 V
Temperature class
T6 / T5
Ambient temperature
T6: –40 °C … +40 °C,
T5: –40 °C … +55 °C
Impact energy
max. 7 J
Ex marking
L II 2G Ex e II T6, T5
L II 2D Ex tD A21 IP66 T80 °C, T95 °C
Approvals
PTB 10 ATEX 1019 X
Weight
396 g

Dimensional drawing

Further drawings

Ex AD 85 MK

Max. number of loaded terminals at Ie max for T6 or T5
Ie Rated operating current

Downloads

Loading...
Choose the type of download
Mounting and wiring instructions – Ex AD

German, English, French, Italian, Portuguese

PDF2 MB 13.11.2025